Gas suppression · CO2 suppression system
High-pressure CO2 total flooding system
- Application
- Total flooding, unoccupied areas only
- Cylinder size, L
- 70–120
- Working pressure
- 5.7 MPa, 15 MPa max
- Discharge
- Within 60 s
- Actuator
- DC 24 V, 1.6 A
- Range
- Cylinders 70, 80, 90, 100, 120 L (45, 50, 58, 65, 76 kg CO2), working pressure 5.7 MPa, max working pressure 15 MPa, max filling ratio 0.65 kg/L, discharge ≤ 60 s, actuator DC 24 V / 1.6 A, -20 to 50 °CWebsite: CO2 suppression system / Total flooding, high pressureLethal at design concentration: unoccupied areas only.
The model and its listing reference are in your offer, so you can check the listing yourself (how to check a listing). Listings belong to the manufacturer.
Have a BOQ or a set of drawings?
Send it today. We reply with a priced offer and our comments on the design, usually within two working days.